Macurco TX-6-ND Nitrogen Dioxide Detector, 12-24 VAC or 12-32 VDC, Dark Gray

  • JMAC SKU: MACURCO-TX-6-ND
$648.98
+ Free Shipping
In Stock
  • Expedited Shipping Available Expedited Shipping Available
  • Need it Tomorrow?
    Need it Tomorrow?
    Select the NEED IT FAST shipping option at checkout and a member of our team will contact you promptly with any available Expedited Shipping options once we receive your order.
JMAC_ID:
200106896
df_manual_boost:
2.05
The Macurco TX-6-ND is a detector, controller, and transducer for monitoring Nitrogen Dioxide Gas in parking garages, maintenance facilities, and many other commercial locations.

This highly sensitive meter can monitor 0-20 ppm of nitrogren dioxide (NO2). When NO2 levels rise, the TX-6-ND automatically activates an exhaust fan to clear the air. The unit is compatible with the Macurco DVP-120 Control Panel and mounts easily to a standard 4 x 4 electrical box.

The TX-6-ND is also available in white.

UPC: 783748825103
Also known as: MA-TX6ND, TX6ND

Technical Specifications:
  • Power: 3 W (max) from 12 to 24 VAC or 12 to 32 VDC
  • Current @ 24 VDC: 75 mA in alarm, 50 mA fan relay on and 23 mA stand by
  • Shipping Weight: 1 pound (0.45 kg)
  • Size: 4 1/2 x 4 x 2 1/8 in. (11.4 X 10.2 X 5.4 cm)
  • Color: Dark gray
  • Connections: plugs/terminals
  • Mounting box: (not included) 4x4 electric
  • Fan relay: 5 A, 240 VAC, pilot duty, SPDT
  • Fan relay actuation: selectable at OFF, 0.2, 0.5, 0.7, 1.0, 1.2, 1.5, 1.7, 2.0, 2.2, 2.5 (default), 2.7, 3.0, 3.2, 3.5, 3.7, 4.0, 4.2, 4.5, 4.7, 5.0 ppm
  • Fan Delay Settings of 0, 1, 3 (default), 5 and 10 minutes
  • Fan Minimum Runtime settings are OFF (default), 3, 5, 10 or 15 minutes
  • Alarm relay: 0.5A 120 V, 60 VA
  • Alarm relay actuation: selectable N.O. default or N.C.
  • Alarm relay settings: 1 - 20 ppm NO2
  • Current Loop, 4-20 mA for 0-20 ppm NO2
  • Operating Environment: 0°F to 125° F (-18°C or above 52°C).10 to 90% RH


For more information about the Macurco TX-6-ND, please contact us.
  • 12-24VAC or 12-32VDC input
  • 5A SPDT Fan control relay
  • 0.5A N.O. or N.C. Alarm Relay
  • Selectable Fan and Alarm Relay Actuation Settings
  • Digital Display (0-20ppm of NO2), Internal Buzzer
  • Coverage Area: 5,000 sq. ft.
  • 4-20mA current loop
  • Supervised system design: detector problem will cause the fan & alarm relay to activate
  • Mounts on a standard 4x4 inch electrical box
  • Factory calibrated

2 Reviews

  • 5
    MACURCO-TX-6-ND

    Posted by 183098 on Apr 6th 2022

  • 5
    MACURCO-TX-6-ND

    Posted by 98894 on May 28th 2016